NH-BV-450/750V---Copper-cored fire resistant electric wire in PVC insulation
NH-BVVB 300/500V---Copper-cored fire resistant flat power cable in PVC insulation & PVC sheath
NH-VV---Copper-cored fire resistant power cable in PVC insulation & PVC sheath
NH-VV22-Copper-cored fire resistant power cable with armored in PVC insulation & PVC sheath
NH-KVV-Copper-cored fire resistant control power cable in PVC insulation & PVC sheath
NH-KVV22-Copper-cored fire resistant control power cable with armored in PVC insulation & PVC sheath
Use:
The products can be used for PVC insulated & fire-resistant cable in A/C rated voltage at 0.6/1kv and below. When it was placed in the firing situation at the fire disaster frequent area, it can still keep working for some time at the fixed laying situation .
1:The fire resistant characteristics of the finished electric wire cable and its testing methods are met the stipulation of GB12666.6. That is :it can not be broken down under the buring flame with 950oC--1000oC or 750oC-800oC at rated voltage. The cable can working 90 minutes or more at the firing temperature of 800oC
2:The finished cables can continuous work without broken for 5 minutes by the 3.5kv voltage testing at 20oC
3:Except the above-mentioned characteristics, the other functions are similar to its corresponding common electronic wire cable.
4:The allowed long-term working temperature of the wire cable is 70oC, the surrounding temperature when laying the cable in the air is not less than 0oC.
The allowed bending radius of the wire cable is showed below :
(1):it should not less than 8 times than the outer diameter of the wire cable when the outer diameter of the wire cable less than 25mm,
(2):it should not less than 12 times than the outer diameter of the wire cable when the outer diameter of the wire cable is 25mm and more.
NH-BV 450/750V
Nominal cross-section
mm2
Conductor wire core
(Root /Single diameter)
mm
Fire resistant layer
Insulating Nominal thickness
mm
InsulatingOuter diameter
mm
Maximum electric resistance at +20oC
km
Minimum insulated electric resistance at +70oC
km
Approximate weight
Thickness
Layer X width
1.5
1/1.38
0.14
2x6
0.8
2.5
12.1
0.011
30
1.5
7/0.52
0.14
2x6
0.8
2.8
12.1
0.010
32
2.5
1/1.78
0.14
2x6
0.8
4.5
7.41
0.010
41
2.5
7/0.68
0.14
2x6
0.8
4.8
7.41
0.009
43
4
1/2.25
0.14
2x8
0.8
5.0
4.61
0.0085
58
4
7/0.85
0.14
2x8
0.8
5.3
4.61
0.007
60
6
1/2.76
0.14
2x10
0.8
5.9
3.08
0.0070
79
6
7/1.04
0.14
2x10
0.8
6.3
3.08
0.0065
83
10
7/1.35
0.14
2x15
1.0
7.2
1.83
0.0065
132
16
7/1.70
0.14
2x20
1.0
8.6
1.15
0.0050
194
25
7/2.14
0.14
2x25
1.2
9.9
0.727
0.0050
294
35
7/2.52
0.14
2x25
1.2
11.5
0.542
0.0045
395
50
19/1.78
0.14
2x30
1.4
12.8
0.387
0.0040
527
70
19/2.14
0.14
2x30
1.4
14.6
0.268
0.0035
726
95
19/2.52
0.14
2x35
1.6
16.9
0.193
0.0035
889
120
37/2.03
0.14
2x35
1.6
18.7
0.153
0.0032
1233
150
37/2.25
0.14
2x40
1.8
20.6
0.124
0.0032
1527
185
37/2.52
0.14
2x45
2.0
22.9
0.0991
0.0032
1880
300
61/2.52
0.14
2x55
2.4
28.7
0.0601
0.0030
3054
400
61/2.90
0.14
2x55
2.6
33.0
0.0470
0.0028
3905
500
61/3.25
0.14
2x55
2.8
36.4
0.0368
0.0026
4840
NH-BVVB 300/500V
Nominal cross-section
mm2
Conductor wire core
(root/Diameter)
mm
Fire resistant layer
mm
Insulating normal thickness
mm
Sheath normal thickness
Outer diameter
mm
Maximum electric resistance at +20oC
km
The minimum insulated electric resistance at the temperature of +70oC